Fire Hydrant Valve

Fire Hydrant Valve

Hydrant is the most important constituent of a Hydrant system. It is used to connect a fire hose pipe to the water pipeline of the building and use pressurized water from the fire hydrant pump to put off medium and big fires in any part of the building. IF&S; provides hydrants made of gunmetal, stainless steel, cast iron, aluminum with different specifications as per the needs of the customer. The standard fire safety rules allow only ISI MARKED Fire hydrants to be used in India. Hydrant valve in India is made according to IS:5290 specification of BIS.

Click Here To Get Free Quote
BRAND IMPACT
Material GUN METAL (LTB-2), CI for hand wheel
Valve Type ISI –TYPE A, Oblique, Flanged Inlet
Pressure Rating Low Pressure Valve
Outlet Size 63 mm
Working Pressure 15 kgf/cm2 (Bar) Maximum
Test Pressure
  • Valve Seat Test for water tightness at 14kgf/cm2
  • Hydraulic test for Body at 21 kgf/cm2
Flange 200mm OD with 16mm Holes
Water Flow Rate 900 litres per min @ 7kgf/cm2Outlet Pressure
Other Complete with Female adapter, PVC blank cap chained with body.